No More Duct Leaks With Our New Three-Part System
Leak-Free gaskets - Leak-free o-rings - Epoxy Caulking
Sealing Joints Between Ducts – It’s a Snap with our Leak-free gaskets
The molded Nitrile gaskets slip easily onto one end of the duct and are connected with a standard Q-F clamp to form a tight and re-useable seal. Note the direction of the airflow when installing the duct.
|

Wipe rolled edge with clean cloth. Then apply a high tack gasket adhesive per the manufacturer’s instructions. High tack gasket adhesives can be purchased locally at industrial or automotive suppliers in either aerosol spray or brushable formulations.
|

Carefully place the gasket along the rolled edge of the part, being careful to avoid kinks or voids. Only one gasket is needed per joint.
|

Join the gasketed end of the pipe to a non-gasketed end of the next part in the ducting run using a standard Q-F clamp. The oil-mist gasket, in addition to the gasket inside the Q-F clamp, provides dual protection against leakage.
|
|
Leak-Free Gasket - Technical Data
|
- General purpose oil resistant polymer
- Preforms well with many oil, water and hydraulic fluid applications
- Good tear resistance
- Available in 4”-10” diameter. Only even sizes in 12”-24” diameter
|
- Should not be used with solvents such as acetone, MEK, ozone, chlorinated hydrocarbons, and nitro hydrocarbons
- Conducts Electricity
|
Classification:
1. ASTM D-2000 M2BG510 A24 B34 EO14 EO34 EF11 EF21
Temperature Range:
Low Temperature Range: -30° F to +225° F
Intermittent: +280° F
|
|
The Q-F Leak Free O-ring for use with our Adjustable-Length Duct
The patented Nordfab “adjustable nipple” provides unlimited flexibility in the length of a duct run.
|
- Cut a standard piece of pipe to length and insert it into the short adjustable nipple section. This assembly will telescope to any length. Place the soft grey o-ring seal onto the cut (inside) piece of pipe and seat it evenly against the rolled metal edge of the adjustable nipple.
- Place the harder black o-ring seal against the outside of the inner grey seal. The order should be as follows:
- rolled edge or nipple; against
- soft, small-diameter o-ring; against
- standard Nordfab o-ring
- Finally clamp the standard Q-F clamp over the rolled metal edge of the adjustable nipple and the hard rolled black o-ring for a leak-free connection. [Make sure both seals fit completely under the clamp and that the air-flows from the cut pipe towards the adjustable nipple].
|
 |
 |
 |
|
O-rings Technical Data
|
|
Leak-Free O-ring

|
- Resists corrosion from weather
- Performs well with many oils and chemicals
- Can’t be damaged by flexing and twisting
|
Classification:
1. ASTM D-1056-68.................SBE43
2. ASTM D-1056-85, 91, 98.........2B3
Temperature Range:
Low Temperature Range: -30oF to 225oF
Intermittent: +280° F
|
|
Standard O-ring

|
- Recommended for petroleum oils and fluids,water, greases, and oils
|
Classification:
1. ASTM D2000 M2BG510 A14 B14 EA14 EO14 EO34 F17
Temperature Range:
Low Temperature Range: -30oF to 225oF
Intermittent: 250° F
|